44
R E P O R T I N G C O D E S
Table 2
Contact ID Zone Alarm/Restoral Event Codes
(as per ADEMCO):
Program any of these codes for zone alarms/restorals when
using the standard (non-automatic) Contact ID reporting format.
Medical Alarms
(1)AA Medical
(1)A1 Pendant Transmitter
(1)A2 Fail to Report In
Fire Alarms
(1)1A Fire Alarm
(1)11 Smoke
(1)12 Combustion
(1)13 Water Flow
(1)14 Heat
(1)15 Pull Station
(1)16 Duct
(1)17 Flame
(1)18 Near Alarm
Panic Alarms
(1)2A Panic
(1)21 Duress
(1)22 Silent
(1)23 Audible
Burglar Alarms
(1)3A Burglary
(1)31 Perimeter
(1)32 Interior
(1)33 24 Hour
(1)34 Entry / Exit
(1)35 Day / Night
(1)36 Outdoor
(1)37 Tamper
(1)38 Near Alarm
General Alarms
(1)4A General Alarm
(1)43 Exp. module failure
(1)44 Sensor tamper
(1)45 Module Tamper
(1)4A Cross Zone Police Code
24 Hour Non-Burglary
(1)5A 24 Hour non-Burg
(1)51 Gas detected
(1)52 Refrigeration
(1)53 Loss of Heat
(1)54 Water Leakage
(1)55 Foil Break
(1)56 Day Trouble
(1)57 Low bottled Gas level
(1)58 High Temp
(1)59 Low Temp
(1)61 Loss of Air Flow
Table 3
SIA Format Automatic Zone Alarm/Restoral Codes
Zone Definition SIA Auto Rep
Codes*
Zone Alm/Rest.
Delay, Instant, Interior, Delay
Stay/Away, Interior Stay/Away,
24Hr Burg.
BA-ZZ/BH-ZZ
Standard 24Hr Fire, Delayed 24Hr
Fire
FA-ZZ/FH-ZZ
24Hr Supervisory US-ZZ/UR-ZZ
24Hr Supervisory Buzzer UA-ZZ/UH-ZZ
24Hr Sprinkler SA-ZZ/SH-ZZ
24Hr Gas GA-ZZ/GH-ZZ
24Hr Heat KA-ZZ/KH-ZZ
24Hr Medical MA-ZZ/MH-ZZ
24Hr Emergency (non-medical) QA-ZZ/QH-ZZ
24Hr Waterflow WA-ZZ/WH-ZZ
24Hr Freeze ZA-ZZ/ZH-ZZ
24Hr Holdup HA-ZZ/HH-ZZ
24Hr Panic PA-ZZ/PH-ZZ
Latching 24Hr BA-ZZ/BH-ZZ
* ZZ = zones 01-08
Section
#
Reporting Code Code Sent When... Dialer
Direction*
Contact
ID Codes
SIA Auto Rep
Codes**
[349-350]
AC Line Trouble/Rest. AC power to control panel is disconnected or interrupted/AC
power restored (Both codes follow AC Failure Comm. Delay.)
MA/R (3) A1 AT-00/AR-00
[349-350]
Main Bell Trouble/Rest. open circuit detected across bell terminals/bell circuit closed MA/R (3) 21 UT-99/UJ-99
[349-350]
Fire Trouble/Rest. a trouble occurs/restores on a fire zone MA/R (3) 73 FT-00/FJ-00
[349-350]
Auxiliary Power Trouble/Rest. aux voltage supply trouble/restoral MA/R (3) AA YP-00/YQ-00
[349]
TLM Failure telephone line monitoring trouble (sent via LINKS. Do not
program if LINKS not used)
MA/R (3) 51 LT-00
[350]
TLM Restore Telephone line trouble restore MA/R (3) 51 LR-00
[349-350]
Gen System Supervisory
Trouble/Rest.
control panel loses/restores communications with module(s)
connected to the Keybus
MA/R (3) 33 ET-00/ER-00
[349-350]
General System Trouble/Restore "Service Required"trouble occurs (view troubles using [*][2][3])/
troubles restored
MA/R (3) 3A YX-00/YZ-00
[351]
Line 1 or 2 FTC Restoral control panel has restored communications to central station on
line 1or 2 (after FTC)
MA/R (3) 54 YK-00
[351]
Event Buffer is 75% Full event buffer is almost full since last upload MA/R (6) 23 JL-00
[351]
DLS Lead In downloading session start MA/R (4) 11 RB-00
[351]
DLS Lead Out downloading session complete MA/R (4) 12 RS-00
[351]
General Zone Trouble/Rest. one or more zones have trouble/trouble restored MA/R (3) 72 UT-00/UJ-00
[351]
Delinquency programmed amount of time (days or hours) for delinquency has
expired without zone activity or without system being armed
MA/R (4) 54† CD-00
[352]
Periodic Test periodic sytem test transmission T (6) A2 RP-00
[352]
System Test [*][6] bell/communications test T (6) A1 RX-00
[352]
LINKS Test LINKS test transmission T (6) A3 TX-00
[353]
General Device Low Battery
Trouble/Rest.
Wireless zones/pendants (WLS908);
handheld keypads (WLS910); wireless keys (WLS909) have low
battery/all low batteries restored
MA/R (3) 84 XT-00/XR-00
* A/R = alarms/restorals;T/R = tampers/restorals; O/C = openings/closings; MA/R = miscellaneous alarms/restorals; T = test transmissions
** UU = user number (user01-42); ZZ = zone number (01-08)
†Program the “Fail to close” event code [(4)54] to report either closing or activity delinquency. Make sure your central station is aware of the application of this
reporting code.