DSC PC1404 v1.1 Guia de Instalação

Consulte online ou descarregue Guia de Instalação para Sistemas de segurança - controlo de acesso DSC PC1404 v1.1. DSC PC1404 v1.1 Installation guide Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 76
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
PC1404 v1.0
Installation Guide
WARNING: This manual contains information on limitations regarding product use and function
and information on the limitations as to liability of the manufacturer. The entire manual should
be carefully read.
Vista de página 0
1 2 3 4 5 6 ... 75 76

Resumo do Conteúdo

Página 1 - Installation Guide

PC1404 v1.0Installation GuideWARNING: This manual contains information on limitations regarding product use and function and information on the limita

Página 2 - IMPORTANT NOTE!

PC14044Keybus Terminals – AUX+, AUX-, YEL, GRN The Keybus is used by the panel to communicate with modulesand vice versa. Each module has four Keybus

Página 3 - 6PRNH'HWHFWRUV

2 Installation2.5 Current Ratings – Modules & AccessoriesIn order for the PC1404 system to operate properly, the poweroutput capabilities of the

Página 4 - Limited Warranty

PC14046Single End Of Line (EOL) Resistors (5600)To enable panel detection of single end of line resistors, Section[013], Options [1] and [2] must be

Página 5 - Table of Contents

2 Installation2.11 Fire Zone Wiring All 4-wire smoke detectors must be wired according to the fol-lowing diagram:All 2-wire smoke detectors must be w

Página 6 - PC1404 Wiring Diagram

PC140483 Keypad CommandsUse any compatible keypad to enter commands and/or program the PC1404 security system. The LED keypad uses function and zonein

Página 7 - 1 Introduction

3 Keypad Commands9[][7][x] Command Functions 1–4[][8][Installer Code] Installer Programming[][9][User Code] No-Entry Arming[][0] Quick Arm (disar

Página 8 - AC, 40VA

PC140410[*][3] Alarm MemoryWhen Disarmed, press [*] then [3] to enter the alarm memory mode. The "Memory" light will flash and any alarm cau

Página 9 - 2 Installation

3 Keypad Commands11[7] Bell Squawk upon Arming/Disarming – This attribute is used to determine whether an access code should generate an arming/dis-ar

Página 10 - Telephone Line Wiring

PC140412Additional Keypad FunctionsThe following additional keypad functions are available:Event Buffer: View the 128-event panel bufferBrightness Con

Página 11 - 2.9 Zone Wiring

4 Programming134 ProgrammingThe PC1404 can be programmed using the following methods:4.1 Installer ProgrammingThe following section of the manual desc

Página 12 - 2.10 Zone Doubling

i6$)(7<,16758&7,216IRU6(59,&(3(56211(/WARNING: When using equipment connected to the TELEPHONE NETWORK, there are basic safety instruct

Página 13 - 2.13 Keypad Zones

PC140414If you are using a pulse communications format, a decimal zero [0] does not transmit. Programming a zero [0] tells the panel not to sendany pu

Página 14 - 3 Keypad Commands

5 Programming Worksheets155 Programming Worksheets5.1 Index to Programming Worksheets and Descriptions Programming Option

Página 15

PC1404 165.2 Programming WorksheetsKeypad Partition/Slot and Function Key Programming[000] Function Key ProgrammingNote: Keypad enrollment must be don

Página 16 - [*][5] Program User Codes

5 Programming Worksheets17[005] System Times[009] Main Board PGM Output Programming (PGM 1 & 2)[010] PC5208 PGM Output ProgrammingValid entries fo

Página 17 - [*][6] – User Functions

PC1404 18[011] PC5204 PGM Output Programming[012] Keypad Lockout OptionsNote: If Keypad Lockout is active, the panel CANNOT be disarmed with a keyswi

Página 18

5 Programming Worksheets19[017] Fifth System Options[018] Sixth System Options[020] Keypad Zone Assignments[022] Ninth System Options[023] Tenth Syste

Página 19 - 4 Programming

PC1404 20[030] Zone Loop Response Options[101]-[108] Zone Attributes [101] Zone 1 Attributes [102] Zone 2 Attributes [103] Zone 3 Attributes [104]

Página 20 - [1][][3], [0]:

5 Programming Worksheets21[170] PGM Output Timer Default 005 I_______I_______I_______I Valid entries are 001-255 seconds[175] Auto-arm Postpone TimerD

Página 21 - 5 Programming Worksheets

PC1404 22[176] Cross Zone/Police Code Timer Default 060 I_______I_______I_______I Valid entries are 000-255 seconds/minutes[181] Auto-Arm Time of DayD

Página 22 - 5.2 Programming Worksheets

5 Programming Worksheets23[329] Priority Alarm and Restore Reporting Codes[330] Tamper Reporting Codes, Zones 01-08 [334] Tamper Restore Reporting Cod

Página 23 - Default Default

LL*XLGHOLQHVIRU/RFDWLQJ6PRNH&2'HWHFWRUVThe following information is for general guidance only and it is recommended that local fire co

Página 24 - *][6] + Installer Prog

PC1404 24[343] Opening (Disarming) Reporting Codes, Access Codes 17-32[344] Miscellaneous Opening (Disarming) Reporting Codes[345] Maintenance Alarm R

Página 25 - [023] Tenth System Options

5 Programming Worksheets25[367] Opening/Closing Communicator Call Directions[375] System Maintenance Alarm/Restore Communicator Call Directions[376] S

Página 26 - Zone Attribute Defaults

PC1404 26[382] Third Communicator Options[383] Fourth Communicator OptionsDLS Downloading[401] Downloading Option Codes[402] DLS Downloading Computer’

Página 27 - Default EU

5 Programming Worksheets27[404] Panel ID Code (Enter 6 Hexadecimal Digits)[405] Answering Machine Double-Call Timer Default 060 I_______I_______I_____

Página 28 - Reporting Codes

PC1404 28Zone Follower PGM requires 2 programming sections for attributes: the normal PGM attribute Sections [501-514] and Sections [551-564] for zone

Página 29

5 Programming Worksheets29[601] Closing (Arming) Reporting Codes, Access Codes 33-40[605] Opening (Disarming) Reporting Codes, Access Codes 33-40INTER

Página 30

PC1404 30Programming PK5500 KeypadsIf you have an PK5500 keypad, additional programming is required for proper operation. All LCD programming is done

Página 31 - Opt Def. ON OFF

Programming PK5500 Keypads31[001]-[008] Zone Labels[071] First User Display MaskDefaultZ o n e _ _ _ _ 1 _ _ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ __BBBB_BBB

Página 32 - DLS Downloading

PC1404 32[072] Second User Display Mask[073] Downloaded LCD Message DurationDefault: 003 _BBBB_BBBB_BBBB_ (Valid entries are 000-255, 000=Unlimited

Página 33 - Attribute:

Programming PK5500 Keypads33[080] PGM Terminal 1[082] Local PGM Output Activation Time[101] Partition 1 Label[102]–[108] Partition 2–8 Labels[120]–[12

Página 34

LLLLimited WarrantyDigital Security Controls warrants the original purchaser that for a period of twelve months from the date of purchase, the product

Página 35 - INTERNATIONAL PROGRAMMING

PC14045.3 Programming Descriptions3URJUDPPLQJ'HVFULSWLRQVThe following is a description of the programming features and options available in t

Página 36 - Programmable Labels

5.3 Programming DescriptionsZone ProgrammingZones 1-8 are enabled by default. Disable unused zones or enable additional zones in Section [001] Zone

Página 37

PC1404[08] Standard 24-hr Fire Zone (hardwired) Note: Do not wire Fire zones on keypad zone terminals if the DEOL supervision option is enabled for

Página 38 - [077] Second Keypad Options

5.3 Programming DescriptionsA bypass of this zone type must be manually removed.With an audible alarm active, using the keyswitch when disarmed is t

Página 39

PC1404[005] System TimesEnter Section [005] then Subsection [01] to program the Entry Delay 1, Entry Delay 2 and Exit Delay for the system. Entries

Página 40 - 5.3 Programming Descriptions

5.3 Programming Descriptions09 System Trouble. This PGM output switches to ground when any of the selected Troubles are detected. The output de-acti

Página 41 - [001] Zone Definitions

PC1404[012] Keypad Lockout OptionsThis section determines how the keypad function operates. The panel can be configured to "lockout" keypa

Página 42

5.3 Programming Descriptions[013] First System Options[014] Second System OptionsOption Description[1] Zone Loop TypeON: Normally Closed Loops. All

Página 43

PC1404[015] Third System Options[016] Fourth System Options[7]Exit Delay Termina-tionExit Delay Termination Enabled. The exit delay will be reduced

Página 44 - [008] Maintenance Code

5.3 Programming Descriptions[017] Fifth System Options [018] Sixth System Options [3] Keypad BlankingON: Blank Keypad When Not Used. If no keys are

Página 45

ivTable of ContentsSafety Instructions for Service Personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 46 - [012] Keypad Lockout Options

PC1404[020] Keypad Zone AssignmentEnter the two-digit zone number to be assigned to each keypad assigned to a specific slot. Only one keypad can be

Página 47 - [014] Second System Options

5.3 Programming Descriptions[030] Zone Loop Response OptionsFast loop response for the onboard zones is programmable using Installer Programming Sec

Página 48 - Annunciation

PC1404[168] Daylight Savings Time BeginsExample: E.g., Set the clock 1 hour ahead at March 5th, 2006 at 2:00am.1. Enter Section [168]. 2. Program t

Página 49

5.3 Programming Descriptions[199] Auto-Arming Pre-Alert TimerIn this section, program the time (in minutes) for the Auto-Arming Pre-Alert time. This

Página 50 - [020] Keypad Zone Assignment

PC1404[330]-[334] Tamper/Restore Reporting Codes, Zones 01-8These reporting codes are used by the communicator to transmit zone tampers and restores

Página 51 - Daylight Savings Time

5.3 Programming DescriptionsFire Trouble & RestoreAn open circuit or any Low Sensitivity, Tamper or Fault report from a wireless smoke detector

Página 52

PC1404[348] Test Transmission Reporting CodesWalk Test Begin/EndThese reporting codes are sent when the walk test is initiated and terminated. These

Página 53

5.3 Programming Descriptions[378] Test Transmission Time of DayThe panel can be configured to communicate a test transmission signal to the monitori

Página 54

PC1404[381] Second Communicator Options[382] Third Communicator OptionsOption Description[1] RingbackON: Opening After Alarm Keypad Ringback Enabled

Página 55

5.3 Programming Descriptions[383] Fourth Communicator Options[401] Downloading Option Codes[7] Residential DialON: Number of Dialing Attempts is 1 f

Página 56 - [377] Communicator Variables

vPC1404 Wiring Diagram200–350 mA931404-112-WIRE AND 4-WIRE SMOKE DETECTORSFor NA installations only1.2, 4, 7 AhLCD5511LED5511PC1555RKZPK5500/PK5501PK5

Página 57

PC1404[402] DLS Downloading Computer’s Telephone NumberThis is a 32-digit hexadecimal programming section. The downloading computer telephone number

Página 58

5.3 Programming Descriptions[551-564] Extended PGM Attributes for PGM Type 29, Zone Follower [551]-[564]The following attributes are available for t

Página 59 - Option Description

PC1404[700] Automatic Clock AdjustThe value entered here adds or subtracts seconds at the end of each day to compensate for inaccuracies in the syst

Página 60 - Access Code Options

5.3 Programming Descriptions[703] Delay Between Dialing AttemptsFor standard (force) dialing, the panel will go off-hook, search for dial tone for 5

Página 61 - [605] Opening by Master Code

PC1404[903] View Module Supervision In this mode, the system displays all of the modules presently enrolled on the system as indicated by the corres

Página 62 - [700] Automatic Clock Adjust

6 Testing & Troubleshooting6 Testing & TroubleshootingTesting:• Power up system• Program options as required (see Section 5 Programming Work

Página 63 - [900] Panel Version

PC1404PC520X Aux Power Supply Trouble • Ensure that a the power supply aux power terminal is not shorted to ground. • Ensure that the maximum power

Página 64

6 Testing & TroubleshootingTrouble [5] Zone Fault Press [5] to determine specific zones with a Fault troubleOpen circuit is present on

Página 65 - Trouble Summary:

PC1404 Appendix A: Reporting Code FormatsThe following tables contain Contact ID and Automatic SIA format reporting codes. See Programming Sections

Página 66 - Trouble [2] AC Failure

Appendix A: Reporting Code Formats[345]-[346] Bell Circuit Trouble/Rest. Software deactivates the bell output if a short is detectedso no additiona

Página 67 - Trouble [7] Not Used

1 Introduction11 IntroductionThis manual provides installation and programming informationfor the PC1404 four-zone panel security system. 1.1 Compatib

Página 68 - &RQWDFW,'

PC1404 Table 3: Automatic Zone Alarm/Restoral Codes=RQH'HILQLWLRQ 6,$$XWR5HS&RGHV&RQWDFW,'$XWR5HS&RGHV&RQWDFW,&apo

Página 69 - 2-wire Smoke Trouble/Rest

Appendix B: Communicator Format OptionsAppendix B: Communicator Format OptionsThe following format options are programmable in Section [350] Communi

Página 70

PC1404 06Residential DialIf Residential Dial is programmed and an event that is programmed to communicate occurs, the panel will seize the line and

Página 71 - DTMF Contact ID

Appendix C: Regulatory Approvals InformationAppendix C: Regulatory Approvals InformationNorth America FCC COMPLIANCE STATEMENTwill provide advance n

Página 74

EuropeThis product is in conformity with:EMC Directive 2004/108/EC based on results using harmonized standards in accordance with article 10(5), R&

Página 75

PC14042Zone Configuration• 31 zone types and 11 programmable zone attributes• Supports up to 4 hardwired NC, SEOL, DEOL zones, expandable to 8 with th

Página 76

2 Installation2 InstallationThe following sections provide a thorough description of how towire and configure devices and zones.2.1 Installation Step

Comentários a estes Manuais

Sem comentários