
34
Restore PC5132 to Factory Default Programming .Section [996]
Restore PC5400 to Factory Default Programming .Section [997]
Restore PC5928 to Factory Default Programming .Section [998]
Restore PC5020 to
Factory Default Programming . . . . . . . . . . . . . . . .Section [999]
5.27 Installer Lockout
If Installer Lockout is selected a hardware default cannot be
performed. If a software default is performed all programming
will restore to factory default.
When Installer Lockout Disable is selected the panel will
restore all programming to factory defaults if a hardware or soft-
ware default is performed on the main control panel.
To enable or disable Installer Lockout perform the following:
1. Enter Installer Programming.
2. To enable Installer Lockout, enter section [990]. To disable
Installer Lockout, enter section [991].
3. Enter the Installer Code.
4. Enter section [990] or [991] again.
Installer Lockout Enable . . . . . . . . . . . . . . . . . . . .Section [990]
Installer Lockout Disable . . . . . . . . . . . . . . . . . . . .Section [991]
5.28 Walk Test
The Installer Walk Test can be used to test the alarm state of
each zone of the panel. The walk test cannot be used to test
zone type [24].
Before beginning the walk test, ensure the following conditions
are met:
1. The panel is disarmed
2. The Keypad Blanking option is disabled (section [016]: [3])
3. The Fire Bell is Continuous option is disabled (section [014]:
[8])
4. The Transmission Delay is disabled, if Transmission Delay is not
required (section [377])
NOTE:
Fire Troubles are not supported in Walk Test.
All outputs will activate for both partitions during the walk
test, regardless of programming.
To perform a Walk Test, do the following:
1. Enter Installer Programming
2. Enter Section [901]
When any zone is violated the panel will activate the Bell Output
for two seconds, log the event to the Event Buffer and communi-
cate the alarm to central station. Each zone should be tested sev-
eral times during the test. Check the event buffer to ensure that
all zones and FAP keys are functioning properly.
NOTE:
The transmission delay timer will affect the commu-
nication of events during walk test mode.
NOTE:
If there is no zone activity on the system for 15 min-
utes, the system will end the walk test and return to the
normal state.
To stop the test, you must do the following:
1. Enter Installer Programming
2. Enter Section [901]
Zones do not have to be restored to stop the test. After the test is
complete, check the Event Buffer to ensure that the Audible/
Silent 24-Hr PGM alarms have been restored.
NOTE:
The Alarm Memory is cleared upon entering Walk
Test mode. When the Walk Test is complete, the Alarm
Memory light will remain lit, but there will be no alarms in
memory. The light will turn off the next time the panel is
armed.
Comentários a estes Manuais