NOTE:
The wireless zone attribute must be enabled for all
enrolled wireless zones.
Zones 1 to 64 Attributes . . . . . . . . . . . . . . Section [101] - [164]
Audible/Silent Alarm . . . . . . . . Section [101] - [164], Option [1]
Pulsed/Steady Alarm . . . . . . . . Section [101] - [164], Option [2]
Activate Chime . . . . . . . . . . . . Section [101] - [164], Option [3]
Bypass Enable . . . . . . . . . . . . . Section [101] - [164], Option [4]
Force Arm Enable . . . . . . . . . . Section [101] - [164], Option [5]
Swinger Shutdown Enable . . . Section [101] - [164], Option [6]
Transmission Delay Enable . . . Section [101] - [164], Option [7]
5.3 Partitions and Zone Assignment
A partition is a limited area of the premises which will operate
independently of another area of the premises. You can create
up to eight partitions on the Power864 system. For example, in
an office/warehouse installation the warehouse area and the
office area can be on separate partitions. With this arrangement,
employee access can be limited to either area.
To set up the system for more than one partition, you must turn
on each partition in section [201].
You can assign any zone to any of the partitions. Global Zones
are zones assigned to more than one partition. A global zone will
only be armed when all assigned partitions are armed. The zone
will be disarmed when any assigned partition is disarmed.
By default, zones 1 through 8 are assigned to partition 1. If addi-
tional zones are being used, or if the application requires more
than one partition, you must program which zones are assigned
to which partitions. You can do this in programming sections
[202] - [265].
NOTE:
Zones programmed as the Null (disabled) zone type
must be removed from all partitions (see section 5.1
“Zone
Definitions
on page 20).
You can assign any Access Code to work on any of the partitions
(see section
“[*] [5] Programming Access Codes
on page 16).
You can assign keypads to work on either a single partition, or on
all partitions (Global operation). See section 2.6
“Keypad
Assignment
on page 8.
Each partition can be programmed to report using a different
Account Number. See section 5.6
“Communicator - Account
Codes
on page 23.
Some of the Programmable Output options are also selectable by
partition. See section 5.12
“Programmable Outputs”
on page
27.
Partition 1 - 8 Enabled/Disabled . . . . . . . . . . . . . .Section [201]
Partition 1 Zone Assignments . . . . . . . . Sections [202] to [209]
Partition 2 Zone Assignments . . . . . . . . Sections [210] to [217]
Partition 3 Zone Assignments . . . . . . . . Sections [218] to [225]
Partition 4 Zone Assignments . . . . . . . . Sections [226] to [233]
Partition 5 Zone Assignments . . . . . . . . Sections [234] to [241]
Partition 6 Zone Assignments . . . . . . . . Sections [242] to [249]
Partition 7 Zone Assignments . . . . . . . . Sections [250] to [257]
Partition 8 Zone Assignments . . . . . . . . Sections [258] to [265]
5.4 Communicator - Dialing
If the Communicator Disable option is selected the panel will
not attempt to call central station. If enabled the panel will
attempt to call central station when an event occurs that has a
valid reporting code programmed (see section 5.8
“Communica-
tor - Reporting Codes”
on page 25). You must also program a
valid telephone number.
Communicator Call Direction Options are used to select
where the panel will send different kinds of reporting codes
when events occur. You can choose to have the panel send
reporting codes to:
1st telephone number (via land line)
2nd telephone number (via land line)
1st telephone number (via LINKS1000)
2nd telephone number (via LINKS1000)
Alternate Communicator (via LINKS2X50)
These options are programmed separately for each type of
reporting code, and for each partition.
The different types of reporting codes are:
Alarm/Restore codes (by partition)
Tamper Alarm/Restore codes (by partition)
Opening/Closing codes (by partition)
System Maintenance Alarm/Restore codes
System Test Transmission codes
If DTMF Dialing is enabled the panel will dial using DTMF (touch
tone). If Switch to Pulse Dial is enabled the panel will switch to
pulse dialing on the 5th attempt to call the central station. If dis-
abled the panel will always dial DTMF.
If DTMF Dialing is disabled the panel will always pulse dial.
The Post Dial Wait for Handshake determines the amount of
time the panel will wait for a valid handshake from the receiver. If
the panel does not hear the handshake it will consider the call a
failed attempt, hang up and try again.
The Maximum Dialing Attempts determines the maximum
number of attempts the panel will make to send a signal to the
central station before indicating a Failure to Communicate (FTC)
trouble condition. The 3rd telephone Number can be used to
back up the 1st in this situation (see section 5.5
“Communicator
- Telephone Numbers
on page 22).
NOTE:Contact your local telephone company to confirm which
settings should be used.
Pulse Dialing. . . . . . . . . . . . . . . . . . . . Section [380], Option [3]
Switch to Pulse Dial . . . . . . . . . . . . . . Section [380], Option [4]
Post Dial Wait for Handshake . . . . . . . . . . . . . . . . Section [166]
Maximum Dialing Attempts . . . . . . . . . . . . . . . . . Section [165]
Communicator Disable . . . . . . . . . . . . Section [380], Option [1]
Communicator Call Direction Options. . . Section [351] to [367]
5.5 Communicator - Telephone Numbers
The panel can call 3 different telephone numbers for communi-
cation to central station. The 1st telephone Number is the pri-
mary number, the 2nd telephone Number is the secondary
number and the 3rd telephone Number will back up the 1st
telephone number if enabled.
NOTE:
The 3rd telephone Number will NOT back up the 2nd
telephone Number.