
4
to supply AC power to the PC2550. The transformer
should not be connected to an outlet that is controlled by
a switch. If AC failure occurs it is displayed as a trouble
on the keypad (see “Keypad Functions [✱][2] Trouble
Conditions”). It can also be transmitted to the monitoring
station as a trouble condition (see “Programming Guide
[✱][8]” sections [12] and [13] for alarm and restore codes
and section [20] for AC transmission delay).
Auxiliary Power Terminals “AUX” and “GND”
The auxiliary power supply can be used to power motion
detectors and other devices requiring 11 V
DC. 400 mA 11
VDC is available from the “AUX” (positive) and “GND”
(negative) terminals when the PC2550 is used with one
keypad. For each additional keypad the auxiliary supply
rating must be reduced by 60 mA. The auxiliary supply is
fused with the keypad supply at 1 amp. Auxiliary fuse
failure transmission can be sent (see [✱][8] sections [12]
and [13]).
Switched Auxiliary Power Terminals
“SW AUX” and “GND”
The switched auxiliary supply can be switched off
momentarily from the keypad (see “Keypad Commands
[✱][4]”). The “SW AUX” terminal is positive and the
“GND” terminal negative. The 400 mA auxiliary supply
rating must be reduced by any current taken from the
switched auxiliary supply. The switched supply shares the
same fuse as the auxiliary supply.
Bell/Siren Terminals “BELL [+]” and “BELL [-]”
These terminals are for powering bells or other devices
requiring a steady output voltage on alarm. The bell
output is fused for 5 amps. When connecting sirens
(speakers with siren driver already built-in), be sure to
observe the correct polarity. Connect the positive lead to
the “BELL [+]” terminal and the negative lead to the
“BELL [-]” terminal.
If no siren or bell is used, connect a 1000 ohm resistor
between “BELL [+]” to “BELL [-]”. The bell/siren alarm
output is pulsed (1 second on 1 second off) when an
alarm is created by the [F] keypad zone, by the FIRE
zone, or when the Bell Pulse option is enabled in section
[18] light 2.
Keypad Terminals “RED”, “BLK”, “YEL” and “GRN”
Connect the four colored wires from the keypads to these
terminals. When connecting more than one keypad,
connect in parallel across the keypad terminals at the
control panel (i.e. all reds wires together, all blacks
together, all yellows together and all greens together).
The keypad red and black power supply terminals are
fused through the auxiliary fuse.
Programmable Output Terminal “PGM OUT”
The operation of the Programmable Output depends
upon which option is selected in the programming table.
See the “Programming Guide” section [30] for a list of
options for the “PGM OUT” output. The “PGM OUT” is a
50 mA maximum switch to ground. A 100 ohm current
limiting resistor is connected in series. A small relay, a
buzzer or other DC operated device may be connected
between the 11 V
DC “AUX” (positive) terminal and the
“PGM OUT” (switched negative) terminal on the main
board.
Auxiliary Input Terminal “AUX IN” (also KEY ARMING)
The “AUX IN” input terminal is a normally open 24 hour
zone. It can be programmed from the keypad to be silent
or audible. There is no display on the keypad for the
“AUX IN” input. An alarm on this input is created by
applying a positive voltage or by closing a contact
between the “AUX IN” terminal and the positive auxiliary
supply. See “Programming Guide [✱] [8]” section [11] for
programming the alarm and restoral codes.
The “AUX IN” terminal can also be used as a momentary
key arming/disarming input. See “Programming Guide”
section [30] for a list of options for the “AUX IN” terminal.
The keyswitch arming feature must be implemented using
a UL listed device.
”FIRE” Zone Input
The “FIRE” zone is a supervised (normally open alarm
initiating contact) end-of-line resistor circuit designed to
accept “Latching” four-wire smoke detectors.
(See “Fire Circuit Installation Diagram”.)
On alarm, (fire zone shorted) the bell output will pulse the
signal to indicate that the fire zone has been activated.
Alarm memory and transmission by the digital
communicator is delayed 30 seconds. If the alarm is
acknowledged, by pressing the [#] key before the 30
second delay has expired the signals will silence and the
transmission will be aborted. If the alarm is not
acknowledged and the 30 second delay expires, the fire
memory latches and the transmission cannot be aborted.
If the smoke detector is not restored to normal after
signal has silenced, the signals will resound after 90
seconds, and 30 seconds after that, the communicator
will transmit. If the signals resound, they may again be
silenced, [#] key, and the communicator will be aborted if
silence occurs within the 30 second delay period.
To restore the smoke detector to normal, clear all
products of combustion from the detector and reset the
detector by pressing [✱] and then holding down [4] for 2
or 3 seconds. This action will remove power from the
smoke detector and if it is clear of smoke, the detector
will return to normal. If the detector is still in alarm, the
signals will sound immediately and the above sequence
will repeat.
For an open on the FIRE zone, the keypad sounder will
beep twice every 10 seconds and the “Trouble” light will
show on the keypad. The communicator will transmit the
trouble condition if programmed for trouble transmission.
The audible trouble signal may be silenced by pressing
Comentários a estes Manuais