[21] Auxiliary Delay Zone Times
Page 21
Default
045
Entry Time (in sec.)
060
Exit Time (in sec.)
[22] Communication Variables
Page 21
Default
03
Maximum transmissions until swinger shutdown
Enter digits from 01 to 99 for number of transmissions per zone during the period as
defined in section [17], 3rd system option code, zone light 7.
“00” = Unlimited transmissions per burglary zone (Fire zone never shuts down).
00
Delay Before Transmission (Burglary Zones only)
Enter digits from 00 to 99 - delay in seconds.
“00” = No delay (Fire zone and 24 hr. zones always transmit without delay).
Transmission delay as programmed here is for burglary zones only.
Note: For UL installations, swinger shutdown cannot be enabled. Each alarm must be transmitted.
For UL residential installations, the delay before transmission must not exceed 15 seconds.
For UL commercial installations, the alarm before transmission must not exceed 00 seconds.
[23] System Clock Times
Page 21
Default
9999
Automatic Arming Time of Day Enter 4 digits from 0 to 9.
9999 For Future Use Do not enter [] or [#].
9999 Test Transmission Time of Day
[24] Installer ’s Code
Page 21
Default Enter 4 digits from 0 to 9.
2550 Do not enter [] or [#].
[25] Master Code
Page 21
Default Enter 4 digits from 0 to 9.
1234 Do not enter [] or [#].
[26] 2nd Master Code
Page 22
Default Can be erased by entering [1111]
AAAA Enter 4 digits from 0 to 9. Do not enter [] or [#].
[27] Downloading Access Code
Page 22
Default Enter 4 digits from 0 to 9.
2525 Do not enter [] or [#].
[28] Panel Identification Code
Page 22
Default Enter 4 digits from 0 to 9.
2501 Do not enter [] or [#].
Note: Valid entries are: 001 to 255.
The maximum delay times for UL residential installations are:
Entry delay = 45 seconds; Exit delay = 60 seconds.
The maximum delay times for UL commercial installations
are:
Entry delay = 60 seconds; Exit delay = 60 seconds.