rchitect’s Specifications
Digital Security Controls
1645 Flint Road, Downsview, Ontario M3J 2J6
The contractor shall provide a complete electrically supervised, battery
backed-up, fire and burglary alarm system. The system shall be complete with a
multi-zone alarm system with the capacity of up to 32 burglar or Class B fire zones
of which up to 32 may be wireless zones. All zones shall be supervised and be
capable of operating listed heat detectors, smoke detectors, alarm contacts,
motion detectors, vibration detectors and other listed fire and burglary alarm
detection devices. The system shall have expansion capability for up to 8 low
current voltage outputs; and 4 high current voltage outputs of which one may be
fully supervised for an additional siren. All outputs shall be programmable to
activate for 1 of 23 options. System shall be complete with a 4 wire unshielded
(QUAD) communications bus that allows system modules and keypads to be
added anywhere on the bus up to 1,000 feet (330m) per leg from the main control
panel. Bus shall be able to withstand temporary shorts of up to +12V without
control panel damage. The system shall be capable of providing up to 1.55 amps
of 12VDC auxiliary power for alarm devices.
The system shall be complete with a built-in power line interface for up to 32
X-10 control devices.
The alarm panel shall be capable of digital communications via regular telephone
lines to two separate monitoring stations or locations with 2 account numbers and
3 telephone numbers. The system communicator shall be capable of
communicating in all major formats including SIA and Contact ID. Events
transmitted shall be programmable to include: fire alarms, burglary alarms,
trouble alarms, supervisory conditions, alarm restoral codes, opening (disarming)
and closing (arming) codes, partial closing codes, and opening after alarm codes.
The system shall be capable of paging personnel on the occurrence of any of the
above events selected by the owner. The system shall be capable of transmitting a
test code to the monitoring station(s) on a programmable daily, weekly or
monthly frequency at a regular time of day.
The system shall be complete with audio interface capable of supporting up to 7
audio ports for local intercom/paging, listen-in broadcast, telephone answering,
audio user help, and 2-way listen-in by the monitoring station.
There shall be a 700mA, PTC protected, supervised bell/siren circuit that will drive
a bell/siren until reset or silenced. Siren output shall be programmable as steady
or pulsed for each zone.
The alarm panel shall be equipped with EEPROM memory to retain all program
information even if all AC and battery power is lost and shall have integral static
and lightning protection circuitry.
To prevent false alarms and unnecessary transmissions to monitoring stations, the
alarm panel shall have SIA false alarm prevention features, programmable swinger
shut down by zone, audible exit delay, audible exit fault, opening after alarm
reporting, arm/disarm bell squawk, urgency on entry delay, “quick exit”,
programmable transmission delay by zone, and transmission delay on AC failure,
TLM trouble, low battery, recent close code, and cross zone police code.
The system shall have stay/away and stay arming capability to allow the user to
remain on the premises while the system is armed. A quick-arm feature shall allow
users without access codes to arm the system and exit. A door chime feature
shall cause the keypad to beep when a selected door is opened or closed.
The system shall support any combination of up to 8 “Language LCD” and “LED”
type keypads with backlit displays. Keypads shall be surface mounted and
capable of fully programming and operating the system. Each keypad shall be
assignable to operate the entire system. Language keypads shall be complete with
32 character liquid crystal display (LCD) to provide plain language
programming instructions, operating instructions, and display of all alarms and
supervisory conditions. They shall be capable of toggling between languages by
pressing a keypad key combination. LED keypads shall have 8 zone indicators. All
keypads shall have keypad activated emergency alarms for panic, emergency, fire,
and duress; 5 programmable function keys; LED indicators for Ready, Armed, and
Trouble; and shall be equipped with a Piezo Buzzer to provide audible feedback for
correct key entries, pre-alert, and trouble.
Each keypad shall have one zone input to allow a zone detector to be wired
directly to the keypad.
System shall support wireless operation with up to 32 wireless panic pendants, 16
wireless arm/disarm keys, and 4 wireless handheld keypads.
The system shall allow any touch-tone phone to be used as a keypad with
programmable voice prompts for system commands, functions, and labels
(zones, etc.).
The system shall allow 39 access codes including 32 user codes, 1 master code,
2 duress codes, 2 supervisor codes, 1 installer code, and 1 maintenance code.
The system shall be uploadable/downloadable to allow programming and
operation from a directly connected local computer, or from a remote computer
over a regular telephone line. Remote access shall be controlled by the owner to
prevent unauthorized access.
The system shall support a 300, 1200, 2400 or 4800 bps serial printer
connected to the communications bus up to 1,000 feet (330m) from the control
panel. The printer shall log all system events and transactions with time and date
stamp. Information shall be stored in the system’s 128 event buffer which can be
examined from the LCD keypad or the via DLS software.
The system shall meet UL standards as required for type of application.
Power / Output Modules
PC5204 Power Supply and 4 High Current
Voltage Output Module
provides 1A @ 12.5VDC for additional modules or
devices connected to the control panel
requires a 16.5VAC 40VA transformer and 4AH battery
includes 4 fully programmable high current voltage outputs
- rated at 300mA @ 12VDC, PTC protected
each output programmable to activate for any of 23 options
one output fully supervised for siren connection
connect up to 1000' (330m) from control panel via KEYBUS
fully supervised for low battery and AC power loss
current draw : 20mA
maximum 1 module per system
PC5208 Low Current Output Module
module provides 8 low current voltage outputs
- rated at 50mA @ 12VDC
each output programmable to activate for any of 23 options
connect up to 1000' (330m) from control panel via KEYBUS
current draw : 50mA
maximum 1 module per system