27
Restore PC5132 to Default Programming . . . . Section [996]
Restore PC5400 Printer to Default ProgrammingSection [997]
Restore Panel to Default Programming . . . . . . Section [999]
5.31 Installer’s Lockout
If Installer’s Lockout is selected, a hardware default cannot
be performed. If a software default is performed, all program-
ming will restore to factory default.
If Installer’s Lockout Disable is selected, the panel will
restore all programming to factory defaults when a hardware
or software default is performed on the main control panel.
To enable or disable Installer’s Lockout, perform the following:
1. Enter the Installer’s Programming mode.
2. Enter the appropriate programming section: [990] or [991].
3. Enter the Installer’s Code.
4. Re-enter the appropriate programming section: [990] or
[991].
Installer Lockout Enable. . . . . . . . . . . . . . . . . . Section [990]
Installer Lockout Disable . . . . . . . . . . . . . . . . . Section [991]
5.32 Walk Test (Installer)
The Installer Walk Test can be used to test the alarm state of
each zone of the panel. The walk test cannot be used to test
zone type [24].
Before beginning the walk test, ensure the following condi-
tions are met:
1. The panel is disarmed
2. The Keypad Blanking option is disabled (section [016]:
[3])
3. The Fire Bell is Continuous option is disabled (section
[014]: [8])
4. The Transmission Delay is disabled, if Transmission
Delay is not required (section [370])
NOTE: Fire Troubles are not supported in Walk Test.
To perform a walk test:
Step 1 - Enter Installer Programming
Step 2 - Enter Section [901]
When any zone is violated the panel will activate the Bell Out-
put for two seconds, log the event to the event buffer and
communicate the alarm to central station.
Test each zone several times. Check the event buffer to
ensure that all zones and FAP keys are functioning properly.
NOTE: Zones with the Force Arm attribute enabled, will not
cause the Ready light to go out when they are violated.
To stop the test:
Step 1 - Enter Installer Programming
Step 2 - Enter section [901]
NOTE: The alarm memory is cleared upon entering Walk Test
mode. When the walk test is complete, the Alarm Memory light
will remain lit, but there will be no alarms in memory. The light
will turn off the next time the panel is armed.
Installer Walk Test Enable/Disable . . . . . . . . . . Section [901]
5.33 Daylight Savings Time
Daylight Savings Time Enabled. At 2:00am on the first Sun-
day in April, the panel clock will be set forward one hour to
3am. At 2:00am on the last Sunday in October, the panel clock
will be set back one hour to 1:00am. Events programmed to
occur between 2:00am and 3:00am will not occur on the last
Sunday in April. Events programmed to occur between 1:00
and 2:00am will occur twice on the last Sunday in October.
Daylight Savings Time Disabled. The panel will make no
automatic time adjustments for Daylight Savings Time.
NOTE: Auto-arm and test transmissions should not be
attempted between 2:00am and 3:00am, as they will be
missed on the first Sunday in April. Events programmed to
occur between 1:00am and 2:00am will occur twice on the last
Sunday in October.