40
Periodic Camera Test
When the Periodic Camera Test option is enabled, the panel will
test cameras connected to a PC5108L module every 30 minutes.
Only cameras with the Camera Test option enabled will be tested.
See your PC5108L Installation Manual for more information on cam-
era tests.
If the Local Mode option is ON, the panel will send events to the
PC5108L Module, Downlook will not be initiated if requested. If the
Local Mode option is OFF, the panel will send communicated events
to the PC5108L Module. Downlook will initiate when requested. See
your PC5108L Installation Manual for more information.See Periodic
Camera Test Section [017], Option [7] and Local Mode Enabled/Dis-
abled Section [381], Option [8]
5.11 Special Installer Instructions PWS Sect 11
[901] - Installer Walk Test Mode Enable / Disable
The Installer Walk Test can be used to test the alarm state of each
zone of the panel. The walk test cannot be used to test zone type
[24]. Before beginning the walk test, ensure the following conditions
are met:
1. The panel is disarmed
2. The Keypad Blanking option is disabled (section [016]: [3])
3. The Fire Bell is Continuous option is disabled (section [014]: [8])
4. The Transmission Delay is disabled, if Transmission Delay is not
required (section [377])
NOTE: Fire Troubles are not supported in Walk Test.
All outputs will activate for both partitions during the walk test,
regardless of programming.
To perform a Walk Test, do the following:
1. Enter Installer Programming
2. Enter Section [901]
When any zone is violated the panel will activate the Bell Output for
two seconds, log the event to the Event Buffer. Check the event
buffer to ensure that all zones and FAP keys are functioning properly.
NOTE: If there is no zone activity on the system for 15 minutes, the
system will end the walk test and return to the normal state.
To stop the test, you must do the following:
1. Enter Installer Programming
2. Enter Section [901]
Zones do not have to be restored to stop the test. After the test is
complete, check the Event Buffer to ensure that the Audible/Silent
24-Hr. PGM alarms have been restored.
NOTE: The Alarm Memory is cleared upon entering Walk Test
mode. When the Walk Test is complete, the Alarm Memory will indi-
cate the zones tested. The Alarm Memory will be cleared the next
time the panel is armed.
NOTE: While the walk test is in progress, all three LEDs (Arm,
Ready, Trouble) will flash at a rapid rate. At the start of the Walk Test,
a TS signal will be communicated. When the test is stopped a TE (test
end) is communicated.
[902] - Reset Module Supervision
All modules will automatically enroll within one minute upon power up
(except the PC5132 if there are no serial numbers programmed). If
modules are to be removed, this section should be entered after the
removal of the modules so that it may clear any supervisory troubles
that may be present. When this mode is entered, the system will re-
evaluate the components of the system.
NOTE: Supervisory requires two%04 commands to enroll a mod-
ule, it may take up to a minute to enroll or delete a module. Before
entering Section [903] to view the module field, this time should be
taken into account.
If there is a module that is not properly communicating with the sys-
tem and this section is entered, the module will be deleted from the
system.
Once executed, all pending Supervisory Trouble Restores will not be
logged or transmitted.
[903] - Module Supervision Field
When this mode is entered, the system will display all of the modules
presently enrolled on the system as indicated below.
[904] - Module Placement Test
Module Selection
Upon entering Section [904], a 2 digit entry will be required to select
the zone number to be tested. Valid entries are 01-32 for Zones 01-
32 respectively. On an LCD Keypad, there are two ways to make a
zone selection: direct entry of “01”-”32”, or by scrolling across to
the description of the module (i.e. “Zone 1”). If a module is selected
that is not enrolled, an error tone will sound.
Placement Indication
After the zone is selected, the alarm contacts must be opened. This
will register a signal strength value that will be indicated and enunci-
ated on all keypads, as well as on the Bell. The system will remain in
this test mode until [#] is pressed or Installer’s timeout (20 minutes).
• GOOD signal will be indicated by Light 1 on an LED keypad or the
word GOOD on an LCD keypad. It will be enunciated on the Key-
pad by 1 beep and on the Bell by 1 Squawk.
• FAIR signal will be indicated by Light 2 on an LED keypad or the
word FAIR on an LCD keypad. It will be enunciated on the Key-
pad by 2 beep and on the Bell by 2 Squawk.
• BAD signal will be indicated by Light 3 on an LED keypad or the
word BAD on an LCD keypad. It will be enunciated on the Key-
pad by 3 beep and on the Bell by 3 Squawk.
• Non-Enrolled zone will be annunciated on the Keypad by an error
tone.
[906] - Local Downlook Remote Trigger
While in this section, either 1 or 2 may be pressed to initiate Down-
look to either Phone Number 1 or 2, respectively. The panel will com-
municate the System Test event, log “Downlook Remote Trigger”,
and transmit the script found in the PC5108L for Remote Trigger.
[990][Installer Code] - Installer Lockout Enable
If enabled, the panel will give a distinctive audible indication on
power up (the phone line relay will click 10 times). This feature will
have no effect on a Software Default (all programming will return to
the factory defaults). However, if a Hardware default is attempted
while lockout is enabled, the default will not occur, and the fraudu-
lent attempt will be logged to the event buffer.
Installer Lockout
If Installer Lockout is selected a hardware default cannot be per-
formed. If a software default is performed all programming will
restore to factory default.
When Installer Lockout Disable is selected the panel will restore all
programming to factory defaults if a hardware or software default is
performed on the main control panel.
To enable Installer Lockout perform the following:
1.Enter Installer Programming.
2.To enable Installer Lockout, enter section [990]
3.Enter the Installer Code.
4.Enter section [990] again.
[903] MODULE SUPERVISION FIELD
Indicator Module
Lights 1-8 Keypads 1-8
Lights 9-14 Zone Expander Groups 1-6
Light 15 PC5100
Light 16 Zone Expander Group 7
Light 17 PC5132
Light 18 PC5208
Light 19 PC5204
Light 20 PC5400
Light 21 PC59XX
Light 22 Alternate Communicator
Light 23 Downlook Module
Light 24 ESCORT 5580
Light 25 Future Use
Light 26-29 PC520X1-4