INSTALLATIONMANUALPC3OOOVersion 7.51
6GUIDELINES FOR SMOKEDETECTOR LOCATIONExperience has shown that all hostile fires in family livingunits generate smoke to a greater or lesser extent.E
7KEYPAD FUNCTIONSIntroductionThe PC3000RK remote keypad provides completeinformation and control of the PC3000 control panel. Thepanel can be fully pr
8the bypass command is entered, pressing [99] recalls thelast zone or group of zones which was bypassed. If thesame group of zones is bypassed each ti
9User’s Programming Commands[Q]+[5]+[MASTER CODE]The [Q][5] user’s programming command is used toprogram additional access codes. Up to 16 user arm-di
10Installer’s Test[Q]+[6]+[MASTER CODE]+[0]This feature is designed to assist the installer in testing thesystem. In this mode, the bell or siren will
11Group B access code, any access code, or no code at all.When the proper keys are pressed the keypad sounder andthe programmable output are activated
12PRINTER SETUPThe PC3000 with version 7.0 or higher software is capableof sending data to a local printer.The printer must be capable of serial commu
13DOWNLOADINGThe PC3000 with version 7.0 or higher software, supportsthe DSC “downloading” package. See the downloadingmanual for details on specific
PROGRAMMINGGUIDE14IntroductionThe PC3000 is programmed by entering instructions fromthe panel keypad. The PC3000 memory is EEPROM andcan be reprogramm
15entering the last digit of the phone number. Press [02] toprogram the next section, enter another section number orpress [#] a second time to return
DOC NOTICENOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment meets ce
16[08] Restoral Reporting CodesZones 9 to 16These reporting codes are used by the communicator totransmit a zone restoral for zones 9 to 16. Use inst
17[14] Reporting Codes for Opening(Disarming) with Access Codes 9 to 16See section [13] for further information.[15] Reporting Codes for Miscellaneous
18programmed for fast 6 =24 Hour buzzerresponse - Do not use 7 =Double delayfast response devices 8 =4 X Delayon these zones. 9 =Daye.g. vibration de
19transmission and periodic download both use the samecycle time which is set in section [22] and the same time ofday as set in section [23]. The test
20Sescoa Super Speed FormatThe Sescoa Super Speed Format must be programmedexactly as follows to function correctly.1.The account code must be four de
21[29] [30] [31] [32] Split Arming“Split Arming” feature permits a single control panel to actas two independent alarm systems, each with its ownopeni
222.Using a short jumper, short pins marked “EEPROMRESET” together.3.Power PC3000 up.4.Wait for 10 seconds. During this time the “Program” lightwill f
23Light on= Only the buzzer will sound during auto-arm(see auto-arm, [Q]+[6]+[Master Code]+[2])[2] Light off= Any key will abort the auto-armLight on=
Note: In sections [01] through [15], do not enter any data in sections that are not used.[01] 1st Phone Number Page 14• Be sure to enter [#] to end
25PC3000 Version 7.51[09] Utility Alarm Reporting Codes Page 16Fire Zone* * Priority alarms/restoralsAuxiliary Input Zone* or *** ** Maintenance ala
TABLE OF CONTENTSSpecifications ____________________________________________________________ 1Features _______________________________________________
26PC3000 Version 7.51[14] Reporting Codes for Opening (Disarming) with Access Codes 9 to 16 Page 16Access Code 9 Access Code 13Access Code 10 Acce
27PC3000 Version 7.51[17] Zone Definitions for Zones 9 to 16 Page 17Note: Zones 9-16 cannot be programmed for fast response - Do not use fast respon
28PC3000 Version 7.51[20] Zones 1 to 8 Bypass Mask Page 18DefaultOn Zone Light 1OnZone Light 2OnZone Light 3OnZone Light 4OnZone Light 5OnZone Light
29PC3000 Version 7.51[25] New Master Code (Access Code Number 1) Page 19Default1 2 3 4 Enter 4 digits from 0 to 9.Do not enter [Q] or [#].[26] Downl
30PC3000 Version 7.51[8] Strobe output (latched alarm output)[9] Failure to communicate output[A] TLM and alarm[B] Courtesy pulse[C] Printer attached[
31PC3000 Version 7.51[31] Access Code Group A Assignment Page 21DefaultOn Zone Light 1OnZone Light 2OnZone Light 3OnZone Light 4OnZone Light 5OnZone
32PC3000 Version 7.51Note: If zone light is on that code can be used tobypass.If an access code is not required to bypass zones, thissection is irrele
33PC3000 Version 7.51[47] Modem Configuration Page 22This section is used to set up the panel for downloading functions. The following table shows t
34PC3000 Version 7.51[51] 3rd System Option Code Page 23Default Zone Light On Zone Light OffOn Zone Light 1 ...Auto-arm - no bell squ
35JUST FOR THERECORDPC3000 Version 7.51Customer _______________________________________________________________________________________________Address
[04] 2nd Account Code ____________________________________________________ 15[05]...[15] Reporting Code Explanation __________________________________
HOOKUP DIAGRAMS36
37KEYPAD AND FIRE CIRCUIT HOOK-UP DIAGRAMSKEYPAD HOOKUP1 Each keypad has four coloured leads: red (RED), black (BLK), yellow (YEL), and green (GRN).
Limited WarrantyDigital Security Controls Ltd. warrants that for a period of twelve months from the date of purchase, the product shall be freeof defe
© 1997 Digital Security Controls Ltd.1645 Flint Rd., Downsview, Ontario Canada M3J 2J6Tel: (416) 665-8460 Fax: (416) 665-7498
29000543 R7
1SPECIFICATIONSControl Panel Specifications21 zones including:• 16 fully programmable supervised zones (EOL resistors)• Supervised fire zone• 1 auxili
2FEATURESKeypad ProgrammingThe PC3000 comes with a default program so it isoperational with a minimum of programming. It is completelyprogrammable fro
3INSTALLATIONBench TestingThe PC3000 contains a factory default program. Anyadditional programming required can be done through thekeypad. For many ap
4Terminal Connections“AC” Power TerminalsUse a 16.5 VAC transformer with a minimum 40 VA rating tosupply AC power to the PC3000. The transformer shoul
5Zone Input Terminals “Z1” to “Z16”Zone inputs “Z1” to “Z16” are supervised end of line (E.O.L.)resistor circuits. Each input must be terminated with