
6
2.7 Programmable Output Wiring
The PGM output is a programmable terminal and will
connect to +12V when activated. The terminal can sink a
maximum current of 50mA. If the desired current is
higher than 50mA, a relay will be required. To connect
the relay, refer to the diagram below:
Each output can be programmed as one of numerous
available output options. See Section 11.4 “Programma-
ble Output Options” for a complete list of PGM output
options.
2.8 AML Device Wiring
Addressable Multiplex Loop (AML) devices use a 2-wire
connection for power and to communicate to and from
the control panel. All detectors are designed for low
power consumption to make for an efficient system.
The system can accommodate up to 56 addressable
devices. Connect the addressable loop to PGM1, when
programmed for AML operation. For instructions on
configuring PGM1 for AML operation, and for AML
device enrollment, see Section 4.4 “Enrolling AML
Devices.”
NOTE: If AML zones are being used, ensure that the
Power Up Shunt option is enabled (default = enabled).
Addressable Devices
The following addressable devices are available:
• AMS-220/220T Smoke Detector with optional temper-
ature sensor*
• AMB-300 PIR Detector
• AMB-500 Ceiling Mount PIR
• AMB-600 Dual PIR Detector
• AMA-100 Glass Break Detector
• AMP-700 Magnetic Door/Window Contact
• AMP-701 Contact Input Module
*Fire alarm devices cannot be placed on the same loop as
burglary devices.
Addressable Loop Response Time
The overall system response time for devices on the
AML loop depends on two criteria: how many loops are
used and how many devices are on each loop.
The response times below include three factors:
• input debounce time
• addressable reporting and confirmation time
• processing time required by the panel to activate the
output
These response times are worst case and typical response
will be faster.
1 to 32 devices on the loop ................................ up to 2.5s
33 to 56 devices on the loop ..............................up to 5.4s
Addressable Loop Current Calculation
The addressable multiplex loop can draw a maximum of
170mA of current from the main panel. In order to deter-
mine the amount of current required for the AML loop,
complete the following chart:
When more AML
devices are added
to a single loop, the
current draw
increases. The loop
wire length must
be limited to the
following dis-
tances depending
on the total loop
current:
Addressable Loop Wiring
AML devices can be
home-run, connected in
a daisy chain, or T-
tapped. Wire the AML
loop according to the
following diagram:
This configuration is
only used for AML
devices. Please see the
installation sheet provided with each device for more
information regarding operation and wiring.
Addressable Loop Current Calculation Chart
Item Current (mA) x Quantity Total (mA)
AMS-220/T 0.8 x
AMB-300 2.5 x
AMB-500 2.5 x
AMB-600 3.5 x
AMA-100 3.5 x
AMP-700 0.8 x
AMP-701 0.8 x
Total Current =
LOOP CURRENT vs. WIRING DISTANCE
Total loop
current (mA)
22 AWG
distance (ft/m)
18 AWG
distance (ft/m)
10 2880/878 5143/1568
20 1620/494 3645/1111
30 1010/308 2520/768
40 771/235 1736/529
50 600/183 1250/381
60 500/152 980/298
70 400/122 800/244
80 321/98 720/220
90 250/76 500/152
100 200/61 310/95
110 165/50 220/67
120 135/41 155/47
130 115/35 130/39
140 106/32 126/38
150 100/30 124/37
160 98/29 122/36
170 96/28 120/35
Comentários a estes Manuais