T-Link Compatibility Chart
Compatible DSC Control Panels
Maxsys PC4020 • Software V3.31 or higher
• Hardware Rev 04B
Power864 PC5020 • Software V3.2 or higher
• Hardware Rev 03
TCP/IP Communicator
T-Link • 10baseT TCP/IP communication module
• Static IP required per module
TCP/IP Communication Routing / Receiver
Reporter IP V2.0 • Required for T-Link communications and DLS
• Supports 255 T-Link accounts, one DLS-3 and
one DLS-3SA at the same time.
• Not for UL Listed installations
• Static IP required for computer
DRL-IP V1.0 * • Required for T-Link communications and DLS
• Supports 255 supervised T-Link accounts, one
DLS-3 and one DLS-3SA at the same time.
• Static IP required per DRL-IP
Downloading Software
DLS-3 V1.3 •Required
• CD from distributor or free download from
dsc.com with a valid password
Maxsys PC4020 V3.3
(with TCP/IP support)
Driver Pack
• Required
• Free download from dsc.com with a valid
password
Power864 PC5020 V3.2
DLS-3 Driver
• Required
• Free download from dsc.com with a valid
password
DLS-3 V1.3 service pack • Free download from dsc.com with a valid
password
System Administration Software
DLS-3 SA V1.3 • Required
• Kit with modem or PC4401 from distributor
DLS-3 SA V1.3 Service Pack 1
for Maxsys V3.31 support
• Required
• Included in the kit or free download from
dscsec.com/dls3drivers.htm
DLS-3 SA V1.3 Service Pack 2
for Power864 v3.2 support
• Required
• Included in the kit or free download from
dscsec.com/dls3drivers.htm
*NOTE:
The DLS software could be used with UL Listed installations only when a service per-
sonnel is on the site.
13
5.2 Standard Connection with PC4020(CF)/PC5020(CF)
WARNING!
All circuits are supervised and power limited. Refer to Battery Lead and AC
Power Lead Routing for UL Listed Commercial Fire Systems diagram for wire
routing. Do not route any wiring over the circuit boards. Maintain at least 1”
(25.4mm) separation between circuit board and wiring.
A minimum of 1/4” (7mm) separation must be maintained at all points
between non power limited wiring and power limited wiring.
Refer to your control panel Installation Manual for any additional information.
Wiring T-Link to a DSC Compatible Control Panel
• Mount the T-Link using bracket or on the side of the cabinet.
• Secure the T-Link module to the cabinet using the supplied standoffs.
• With both AC and battery disconnected removed from the DSC control panel,
wire the T-Link to the panel using 4 wires from the PC-Link of the panel to the
"PANEL" connector on the T-Link.
• Wire the panel's AUX + and - to 12V and GND terminals of T-Link.
• Apply AC and DC to the main control panel. Both the T-Link and the panel
should power up.
• Do the necessary programming that is required.
NOTES: If a Bell/Siren is not going to be used, wire the Bell/Siren terminals
on the panel with a 1000 ohm resistor.
For Commercial Fire installation, when a bell/siren is used in the applica-
tion, it should be connected to the DSC module PC4702BP.
Please refer to the PC4020 Installation Manual. The keypad or any other
accessory connected to the Combus shall be connected within 3 feet / 0.9 m
and in conduit.
!